Standard Efficiency, Standard IPLV
SP Circuit Breaker w/Lockable Handle
Control Transformer
Non-powered Convenience Outlet
N American Safety Code (cUL)
Service Isolation Valve (Suction)
Compressor Heaters
One Differential Pressure Switch per Chiller
ASME & CRN Pressure Vessel Rated
Pre-coated Fin Condenser Coil, Slit Fins
Louvered (Condenser Only) Enclosure Panels
Low Sound Fans
York Chiller Model Number YCIV0287(1)
Ambient Operating Range 0-125oF
Chilled Water Setpoint Limits 44-54 oF
Refrigerant Circuits 3
Refrigerant weight – R134a 524.8 Lbs.
Equipment Insurance Value 190,000
DIMENSIONS (Trailer Mounted)
Length 48’
Width 8’ 6”
Height 13’
Total weight w/trailer 40,765 lbs
ELECTRICAL DATA
Single Point Power Supply 460V / 3∅ / 60Hz
Connections (4 per ∅) Series 16 Cam Type
Running Load Amps 455A*
Minimum Circuit Ampacity 494A*
*Add 30A if using 20hp pump option
EVAPORATOR FLOW
Minimum 282 GPM
Nominal 653 GPM
Maximum 1,205 GPM
Fluid connections 6”, Grooved
Maximum Water Side Pressure 150 PSIG